|
Inspection - Housing Quality Standards
1.0 Living
Room
Ceiling
– A ceiling that is in good condition.
Walls
– Walls that are in good condition.
Electricity
– At least two electric outlets, or one outlet and one permanent
overhead light fixture. Do not count table or floor lamps,
ceiling lamps plugged into a socket, and extension cords: they
are not permanent.
-
Not acceptable are broken or frayed
wiring, light fixtures hanging from wires with no other firm
support (such as a chain), missing cover plates on switches
or outlets, badly cracked outlets.
-
Outlets shall be tested for proper
grounding, if installing GFCI’s make sure they operate
correctly.
Floor
– A floor that is in good condition.
Windows
– At least one window. Every window must be in good condition.
-
Not acceptable are windows with badly
cracked, broken or missing panes, and windows that do not
shut or, when shut, do not keep out the weather.
Lock
– A lock that works on all windows and doors that can be reached
from outside, a common public hallway, a fire escape, porch or
other outside place that cannot be reached from the ground. A
window that cannot be opened is acceptable.
Paint
– No peeling, flaking, cracking, chalking or chipping paint if
you have children under the age of six and the house or
apartment was built before 1978.
2.0
Kitchen
Ceiling
– A ceiling that is in good condition.
Storage
– Some space to store food.
Electricity
– At least one electrical outlet and one permanent light
fixture. Do not count table or floor labels, ceiling lamps
plugged into a socket and extension cords. They are not
permanent.
-
Not acceptable are broken or frayed
wiring, light fixtures hanging from wires with no other firm
support (such as a chain), missing cover plates on switches
or outlets, badly cracked outlets.
-
Outlets within 6 feet of the kitchen sink
that service the counter must be GFCI protected. Non GFCI
receptacles on the same circuit with an existing GFCI
receptacle must have printed labels on the cover indicating
they are “GFCI Protected”.
Stove and
Oven - A stove (or range) and oven that
works (This can be supplied by the tenant)
Floor
– A floor that is in good condition. Not acceptable are large
cracks or holes, missing or warped floorboards or covering that
could cause someone to trip.
Preparation
Area - Some space to prepare food
Paint
- No peeling, flaking, cracking, chalking or chipping paint if
you have children under the age of six and the house or
apartment was built before 1978.
Window
– If there is a window, it must be in good condition
Lock
– A lock that works on all windows and doors that can be reached
from outside, a common public hallway, a fire escape, porch or
other outside place that cannot be reached from the ground. A
window that cannot be opened is acceptable.
Walls
– Walls that are in good condition
Serving
Area - Some space to serve food A separate
dining room or dining area in the living room is alright.
Refrigerator - A refrigerator that keeps
temperatures low enough so that food does not spoil. (This can
be supplied by the tenant)
Sink
- A sink with hot and cold running water
3.0
Bathroom
Ceiling
– A ceiling that is in good condition.
Window
– A window that opens or a working exhaust fan.
Lock
– A lock that works on all windows and doors that
can be reached from outside, a common public hallway, a fire
escape, porch or other outside place that cannot be reached from
the ground. A window that cannot be opened is acceptable.
Toilet
– A flush toilet that works.
Tub or
shower – A tub or shower with hot and cold
running water.
Floor
- A floor that is in good condition.
Paint
– No peeling. flaking, cracking, chalking or chipping paint if
you have children under the age of six and the house or
apartment was built before 1978.
Walls
– Walls that are in good condition.
Electricity
– At least one permanent overhead or wall light fixture.
-
Not acceptable are broken or frayed
wiring, light fixtures hanging from wires with no other firm
support (such as a chain), missing cover plates on switches
or outlets, badly cracked outlets.
-
Outlets within 6 feet of the bathroom
sink and bathtub must be GFCI protected. Non GFCI
receptacles on the same circuit with an existing GFCI
receptacle must have printed labels on the cover indicating
they are “GFCI Protected”.
-
Outlets shall be tested for proper
grounding, if installing GFCI’s make sure they operate
correctly.
Sink
– A sink with hot and cold running water.
4.0
Other Rooms Used for Living
These include bedrooms, dens, halls, and
finished basements or enclosed, heated porches. The
requirements for other rooms that are lived in are similar to
the requirements for the living room as explained below.
Other Rooms
Used for Living Must Have:
Ceiling
– A ceiling that is in good condition.
Walls
– Walls that are in good condition.
Paint
– No peeling, flaking, cracking, chalking or chipping paint if
you have children under the age of six and the house or
apartment was built before 1978.
Electricity
in Bedrooms - At least two electric
outlets, or one outlet and one permanently installed light
fixture. Do not count table or floor lamps, ceiling lamps
plugged into a socket, and extension cords: they are not
permanent.
-
Not acceptable are broken or frayed
wiring, light fixtures hanging from wires with no other firm
support (such as a chain), missing cover plates on switches
or outlets, badly cracked outlets.
-
Outlets shall be tested for proper
grounding, if installing GFCI’s make sure they operate
correctly.
Floor
- A floor that is in good condition. Not
acceptable are large cracks or holes, missing or warped
floorboards or covering that could cause someone to trip.
Lock
– A lock that works on all windows and doors that can be reached
from outside, a common public hallway, a fire escape, porch or
other outside place that cannot be reached from the ground. A
window that cannot be opened is acceptable.
Windows
– At least one window. Every window must be in good condition.
Not acceptable are windows with badly cracked, broken or missing
panes, and windows that do not shut or, when shut, do not keep
out the weather.
Other rooms that are not lived in may be a
utility room for washer and dryer, basement or porch. These
must be checked for security and electrical hazards and other
possible dangers (such as walls or ceilings in danger of
falling), since these items are important for the safety of the
entire apartment. You should also look for other possible
dangers such as large holes in the walls, floors, or ceilings,
and unsafe stairways. Make sure to look for these things in all
other rooms not lived in.
Basement
Paint
– No peeling, flaking, cracking, chalking or chipping paint if
you have children under the age of six and the house or
apartment was built before 1978.
-
This includes exterior walls, stairs,
decks, fences, porches, railings, windows, outbuildings and
doors.
Cooling
- Some windows that open, or some working ventilation or cooling
equipment that can provide air circulation during warm months.
Plumbing
- Pipes that are in good condition, with no leaks and no serious
rust that causes the water to be discolored.
Water
Heater - A water heater located, equipped
and installed in a safe manner along with a discharge line that
extends to within six inches of the floor.
Heat
- Enough heating equipment so that the unit can be made
comfortably warm during cold months.
Smoke
Detectors - At least one working smoke
detector on each level of the unit, including the basement and
finished attics. Smoke detectors must be located inside or
outside of each bedroom. If bedrooms are not close together,
more than one smoke detector may be required per floor. If
detectors are located on the ceiling, the edge must be at least
4 inches from the wall. If located on the wall, the top edge of
the detector must be between 4 and 12 inches from the floor.
Detectors also must be at least 3 feet from kitchen and bathroom
doors. If any member of your family is hearing impaired, the
smoke detector must have an alarm designed for hearing impaired
persons.
Stairs and
Hallways - Interior stairs with railings
and common hallways that are safe and in good condition. If
stairs are open on both sides, 2 handrails are required.
Pollution
- No serious air pollution, such as exhaust fumes or sewer gas.
Rodents and
Vermin - No sign of rats or large numbers
of mice or vermin (like roaches).
Foundation
- A foundation in good condition that has no serious leaks.
Water
Supply - A plumbing system that is
connected to an approvable public or private water supply
system.
Sewage
- A plumbing system that is connected to an approvable public or
private water supply system.
Chimneys
- No serious leaning or defects (such as big cracks or missing
bricks) in any chimneys.
Electricity
– Outlets within 6 feet of a water source such as a washer, sump
pump, etc. must either be a GFCI receptacle, a GFCI protected
receptacle or a single receptacle instead of a duplex.
Health and Safety
Smoke
Detectors – At least one working smoke
detector on each level of the unit, including the basement and
finished attics. Smoke detectors must be located inside or
outside of each bedroom. If bedrooms are not close together,
more than one smoke detector may be required per floor. If
detectors are located on the ceiling, the edge must be at least
4 inches from the wall. If located on the wall, the top edge of
the detector must be between 4 and 12 inches from the floor.
Detectors also must be at least 3 feet from kitchen and bathroom
doors. If any member of your family is hearing impaired, the
smoke detector must have an alarm designed for hearing impaired
persons.
Fire Exits
– The building must provide an alternate means of exit in case
of fire (such as stairs or exit through windows, with the use of
a ladder if windows are above the second floor).
Elevators
– Make sure the elevators are safe and work properly.
Entrance
– An entrance from the outside of from a public hall, so that it
is not necessary to go through anyone else’s private apartment
to get into the unit.
Neighborhood - No dangerous places, spaces,
or things in the neighborhood such as:
Garbage
- No large piles of trash and garbage inside or outside of the
unit, or in common areas such as hallways. There must be a
space to store garbage (until pickup) it must be covered tightly
so that rats and other animals cannot get into it. Trash should
be picked up regularly.
Lights
- Lights that work in all common hallways and interior stairs.
Stairs and
Hallways - Interior stairs with railings,
and common hallways that are safe and in good condition. If
stairs are open on both sides, 2 handrails are required.
Plumbing
- Pipes that are in good condition, with no leaks and no serious
rust that causes the water to be discolored.
Pollution
- No serious air pollution such as exhaust fumes or sewer gas.
Rodents or
Vermin - No sign of rats or large numbers
of mice or vermin (like roaches).
Manufactured Home: Tie Downs - Manufactured
homes must be placed on site in a stable manner and be free from
hazards such as sliding or wind damage.
Electricity
– Breaker boxes cannot have open spaces. Open spaces must have
proper snap-in blank covers and all wires going into electrical
boxes and junction boxes must be secured with wire clamps. All
junction boxes must have blank covers installed.
Building
Exterior, Plumbing and Heating
The building must have:
Roof
– A roof in good condition that does not leak,
with gutters and downspouts, if present, in good condition and
securely attached to the building.
Outside
handrails – Secure handrails on any
extended length of stairs (four or more steps) and any porches,
balconies, or decks that are 30 inches or more above the
ground. If steps are open on both sides, 2 handrails are
required.
Walls
– Exterior wall that are in good condition, with no large holes
or cracks that would let a great amount of air inside.
Foundation
– A foundation in good condition that has no serious leaks.
Water
Supply - A plumbing system that is
connected to an approvable public or private water supply
system.
Sewage
- A plumbing system that is connected to an approvable public or
private water supply system.
Chimneys
- No serious leaning or defects (such as big cracks or missing
bricks) in any chimneys.
Paint
- No peeling, flaking, cracking, chalking or chipping paint if
you have children under the age of six and the house or
apartment was built before 1978.
-
This includes exterior walls, stairs,
decks, fences, porches, railings, windows, outbuildings and
doors.
Cooling
- Some windows that open or some working ventilation or cooling
equipment that can provide air circulation during warm months.
Plumbing
- Pipes that are in good condition, with no leaks and no serious
rust that causes the water to be discolored.
Water
Heater - A water heater located, equipped
and installed in a safe manner along with a discharge line that
extends to within six inches of the floor.
Heat
- Enough heating equipment so that the unit can be made
comfortably warm during cold months.
Electricity
– exterior receptacles must be GFCI protected and must be
installed in weather tight electrical boxes with covers.
|